If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual TOSHIBA RAV-SM1603AT-E. We hope that this TOSHIBA RAV-SM1603AT-E user guide will be useful to you.
You may also download the following manuals related to this product:
TOSHIBA RAV-SM1603AT-E INSTALLATION MANUAL (2045 ko)
TOSHIBA RAV-SM1603AT-E DOCUMENTATION COMMERCIALE (1545 ko)
TOSHIBA RAV-SM1603AT-E DATA BOOK (1533 ko)
TOSHIBA RAV-SM1603AT-E INSTALLATION MANUAL (1856 ko)
Manual abstract: user guide TOSHIBA RAV-SM1603AT-ESERVICE MANUAL
Detailed instructions for use are in the User's Guide.
[. . . ] A07-009
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
OUTDOOR UNIT <DIGITAL INVERTER>
RAV-SM1603AT-E RAV-SM1603ATZ-E RAV-SM1603ATZG-E
INDOOR UNIT <DIGITAL INVERTER>
RAV-SM1403DT-A RAV-SM1603DT-A
Refer to the Service Manual with File No. A06-010 for Model RAV-SM1403AT-E, and refer to the Service Manual with File No. A07-003 for Model RAV-SP1403AT-E, respectively.
R410A
PRINTED IN JAPAN, Jun, 2008 ToMo
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. The cleaning diagram for the air filter is there for the service person, and not for the customer.
CONTENTS
SAFETY CAUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] (Check code is not output. ) However, if the above error is detected during the automatic address set mode, a check code may be output.
[L09 error]
Is not yet capacity setting of indoor unit set up?Defect Replace
75
[L20 error]
Are wiring connections to communication lines U3 and U4 normal?YES YES Correct central control system address.
NO Correct wiring connection.
Is not the multiple same central control system addresses connected?NO
Check central controller (including network adapter) and indoor P. C. Defect Replace
[L30 error]
NO
Are outside devices of connector CN80 connected?Defect Replace
Check cause of operation.
[P30 error] (Central controller)
NO Is group operation carried out?YES
Is there check code on sub remote controller in main and sub remote controllers?YES
NO
Check corresponding indoor unit/outdoor unit.
Check indoor P. C. Defect Replace
76
[P10 error]
Is connection of float switch connector (Indoor control board CN34) normal?NO YES
NO
Correct connection of connector.
Check and correct wiring and wire circuit.
NO Does drain pump work?YES NO Are connector pins 1 and 2 at drain pump unit side shorted (Resistance value 0)? YES
Check the drain pipe, etc.
Replace drain pump and indoor P board . C. Defect Replace
Check that voltage of 1-2 pin of CN504 on the indoor P board is +12V. (1 pin is plus (+). ) . C.
[F10 error]
NO Correct connection of connector.
Is connection of TA sensor connector (CN104 on indoor P board) correct? Refer to TA sensor (Temperature-Resistance value characteristic table)
Check indoor P board (MCC-1403). Defect Replace
77
[P19 error]
Temperature sensor check TE sensor CN601 TS sensor CN600 Indoor TC sensor Defect Correct and repair
Is operation of 4-way valve normal?in cooling/heating operation. ) NO
YES
Is the coil resistance value of 4-way valve between 1. 3 and 1. 6k?YES
NO
Replace coil of 4-way valve.
Check operation of outdoor P. C. board operation (Self-hold valve type : SP110, SP140)
1) Set SW804 of Dip switch as the following figure and then push SW801 for approx. · When checking again, check operation 1 minute or more after the first check because exothermic of part (Coil, resistance R700) is large. (There is no problem when coil is not connected. ) 2) After check, turn off all the Dip switch SW804.
Exchange to cooling cycle
Exchange to heating cycle
SW804 SW801
1234
CN701 1
SW804 SW801
1234
CN701 1
ON
4 DC200V or more
ON
Push
Push
4 DC200V or more
Note) Check by tester Analog tester : Good if over DC200V Digital tester : Good if Max. value is over DC200V though the varied value may be displayed.
78
[F02 error]
Is connection of TC sensor connector (CN101 on Indoor P board) correct? [. . . ] (Bind with crossed right-up)
Bundling band
Fan motor lower lead
Terminal block fixing plate
4-way valve lead
149
15. Indoor Unit
RAV-SM1403DT-A, RAV-SM1603DT-A
213 205
208
204 207 211
207
209
213
202
212 201 203 206 214 210 215 216
150
Location No. 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216
Part No. 43172203 4312C041 43019830 43020352 43020353 43170244 43139167 43139154 43139155 43179135 431S8089 4314J404 43122118 43166011 43166004 43166005
Description Pan Ass'y, Drain Motor, Fan, AC240V, 50Hz, 600W Bushing Fan Fan Hose, Drain, 25A Bell Mouth Band, Motor, Left Band, Motor, Right Band, Hose, 37-40 Owner's Manual Refrigeration Cycle Ass'y Case Ass'y, Fan Remote Controller, SX-A4EE Remote Controller, SX-A11JE2 Remote Controller, EX-W2JE2 1 1 1 1 1 1 2 2 2 1 1 1 2 1 1 1
Model Name RAV-SM1403DT-A RAV-SM1603DT-A 1 1 1 1 1 1 2 2 2 1 1 1 2 1 1 1
151
RAV-SM1403DT-A, RAV-SM1603DT-A
411
403, 413
401 402
406
412 404, 410
405 409
408
407
Location No. [. . . ]