User manual TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702. We hope that this TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702 user guide will be useful to you.


TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702 : Download the complete user guide (1036 Ko)

Manual abstract: user guide TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702

Detailed instructions for use are in the User's Guide.

[. . . ] 7/02 TJERNLUND PRODUCTS, INC. 1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 · (651) 426-2993 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com INCLUDES NEW UC1 UNIVERSAL CONTROL MODEL SS1 INSTALLATION INSTRUCTIONS !Recognize this symbol as an indication of important Safety Information! OWNER INSTRUCTIONS, DO NOT DESTROY NOTE: FLUE GAS TEMPERATURES MUST NOT EXCEED 650oF AT VENT SYSTEM INLET. THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL INJURY OR PROPERTY DAMAGE. DO NOT DESTROY. [. . . ] Connect #2 on UC1 terminal block to C on internal control terminal strip of furnace/boiler. Connect #4 on UC1 terminal block to W on internal control terminal strip of furnace/boiler. 15 SIDESHOT WITH INTEGRAL UC1 CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITION MODULE IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE. SPARK (9) (8) J2 OR 115V UNIVERSAL CONTROLLER DRY CALL JUMPER 24V J1 (7) 24V 24V GND BNR GND PV MV / PV MV (6) (5) (4) (3) (2) (1) PI YE GR YE WH OR WH OR YE SUPPLY 115 VAC 50/60 Hz R XL XN PV PV MV MV GROUND HONEYWELL IGNITION CONTROL GR IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN ELECTRICAL BOX. LEGEND: 115 VAC 24 VAC GAS VALVE D/N 9183046-8 1. Remove the wire on MV at gas valve and connect it on #1 on UC1 terminal block. Make sure RED voltage jumper on UC1 is on 24V. SIDESHOT WITH INTEGRAL UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 OR 115 VAC STANDING PILOT INTERNAL CONTROLS OF FURNACE/BOILER B2 COM Aquastat T-stat B1 HOT 115V IMPORTANT: RED JUMPER POSITION MUST BE THE SAME AS APPLIANCE INTERLOCK VOLTAGE. DRY CALL JUMPER J2 J1 UNIVERSAL CONTROLLER 24V COM TR HOT TH SUPPLY 115 VAC 50/60 Hz GROUND IMPORTANT: CRIMP GROUND WIRE TO GROUNDING SPADE TERMINAL IN ELECTRICAL BOX. XL XN LEGEND: 115 VAC 24 OR 115 VAC D/N 9183046-1 24V OR 115V GAS VALVE 1. Remove the wire on TH or HOT of gas valve and connect it on #1 on UC1 terminal block. Make sure RED voltage jumper on UC1 is on 24V or 115V depending on control voltage. 16 DRAFT ADJUSTMENT PROCEDURE NOTES: All draft adjustments are approximate. Subsequent draft adjustments may be required to compensate for various field conditions: wind, vent pipe resistance, building pressure, multiple appliances, etc. BTU/HR input ratings assume 30% or less excess air for flame retention burners and 50% to 100% excess air for conventional oil burners. Do not exceed the recommended BTU/HR input range of the SideShot. Under no circumstances shall the minimum draft adjustment be used for the larger input range of this product. Improper draft adjustment may result in the dispersion of flue products/carbon monoxide into the building interior. DIAGRAM P DRAFT ADJUSTMENT PROCEDURE FOR OIL EQUIPMENT The SideShot Vent system will properly vent a wide range of BTU/hr. To compensate for different burner capacities, vent connector lengths and wind conditions it features a draft adjustment located on the outside of the Vent Hood. In general, positioning the draft adjustment inward will cause the SideShot to operate at lowest capacity. Positioning the draft adjustment outward will cause the SideShot to operate at highest capacity. IMPORTANT: The following paragraph describes the initial draft adjustment. It may be necessary to make a slight readjustment to compensate for various conditions: wind, vent connector resistance, negative building pressure and multiple appliances. ASHRAE lists the average design factor for wind loads in North America at 15 MPH. We recommend that the 25 MPH category be used to allow for excursions beyond the 15 MPH average. It is not recommended for the SideShot to be terminated on a wall that faces the direction of the prevailing winds. Backdrafts by severe winds can cause oil odors to remain in the structure and/or interrupt heating equipment operation. [. . . ] Date of original installation and dates any service work was performed. Details of the problem as you can best describe them. 22 LIMITED PARTS WARRANTY AND CLAIM PROCEDURE Tjernlund Products, Inc. warrants the components of the SideShot for two years from date of installation. This warranty does not cover normal maintenance, transportation or installation charges for replacement parts or any other service calls or repairs. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702




Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual TJERNLUND SS1 SIDESHOT WITH UC1 UNIVERSAL CONTROL (VERSION X.02) 8504102 REV 0702 will begin.

 

Copyright © 2015 - manualRetreiver - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.