User manual TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996. We hope that this TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996 user guide will be useful to you.


TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996 : Download the complete user guide (38 Ko)

Manual abstract: user guide TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996

Detailed instructions for use are in the User's Guide.

[. . . ] DIAGRAM A1 TJERNLUND PRODUCTS, INC. 1601 Ninth Street · White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 · (651) 426-2993 · FAX (651) 426-9547 Visit our web site · www. tjernlund. com L-185 SAFETY INTERLOCK SYSTEM (P/N 950-2064) (For Millivolt and 24 Volt Control Systems only) This Safety Interlock System may be used on conventional chimney or Power Vented appliances equipped with a draft hood, draft diverter or draft control. DIAGRAM A2 PURPOSE To provide a means for appliance shut-down in the event of flue blockage or down drafts. OPERATION The Linear Limit Spillage Sensor circuit is "normally closed" and will not affect normal appliance operation. When concentrated spillage of combustion gases occurs from the draft hood, diverter or barometric control, the Linear Limit Spillage Sensor circuit will open preventing burner operation. PARTS LIST QUANTITY (1) (1) (1) DESCRIPTION Linear Limit Spillage Sensor with manual reset, 185o set point and six foot cable Linear Limit mounting packet Wire routing packet DIAGRAM A3 INSTALLATION NOTE: DO NOT CUT THE COPPER CAPILLARY SENSING TUBE!! [. . . ] Using cable routing tabs from wire routing packet, attach Linear Limit control cable to appliance maintaining a safe distance from hot surfaces, e. g. appliance vent pipe and hot water pipes. 3b. 4. SAFETY INTERLOCK TEST 1. Remove vent connector from vent breaching at joint above Linear Limit Spillage Sensor, (See Diagram C1). Block vent connector with sheet metal or other non-combustible material, (See Diagram C2). RESULT: Spillage will emit from draft hood, diverter or barometric control. In less than two minutes, Linear Limit Spillage Sensor will open, preventing thermostat signal from reaching burner. 4. COMBUSTION AIR TEST The L-185 Linear Limit Safety Interlock System is designed to alert the user to a potentially hazardous condition. It is not designed to, and cannot replace regular chimney inspection, appliance servicing and combustion testing. DO NOT USE THE L-185 AS A SUBSTITUTE FOR PROFESSIONAL APPLIANCE MAINTENANCE. If appliance is installed in utility room or closet, close the entrance door to this room. [. . . ] Return all windows, doors and fans to their previous conditions of use. DIAGRAM C2 2. 3. 4. 5. 6. NOTE: For further assistance contact the Tjernlund Products, Inc. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996




Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual TJERNLUND 950-2064 L-185 SAFETY INTERLOCK KIT 8504020 REV 3 0996 will begin.

 

Copyright © 2015 - manualRetreiver - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.