Detailed instructions for use are in the User's Guide.
[. . . ] Z906-E1-07
DeviceNet Safety NE1A Series: NE1A-SCPU01(-V1)(-EIP)/ -SCPU02(-EIP)
Safety Network Controller
OPERATION MANUAL
NE1A Series Safety Network Controller: NE1A-SCPU01(-V1)(-EIP)/-SCPU02(-EIP) Operation Manual
Revised July 2009
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual. The following conventions are used to indicate and classify precautions in this manual. Failure to heed precautions can result in injury to people or damage to property.
!WARNING
Indicates a potentially hazardous situation which, if not avoided, will result in minor or moderate injury, or may result in serious injury or death. Additionally, there may be significant property damage.
Indicates general prohibitions for which there is no specific symbol.
Indicates general mandatory actions for which there is no specific symbol.
OMRON Product References
All OMRON products are capitalized in this manual. [. . . ] Up to eight input conditions can be evaluated.
Optional Input Settings
The number of inputs can be increased on the In/Out Setting Tab Page in the function block property dialog box.
Parameter Number of inputs Setting range 1 to 8 Default setting 2
143
Command Reference: Logic Functions Truth Tables
Truth Table for One-input AND Evaluation
Input 1 0 1 Output 1 0 1
Section 8-4
0: OFF, 1: ON Truth Table for Two-input AND Evaluation
Input 1 0 x 1 Input 2 x 0 1 Output 1 0 0 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Three-input AND Evaluation
Input 1 0 x x 1 Input 2 x 0 x 1 Input 3 x x 0 1 Output 1 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Four-input AND Evaluation
Input 1 0 x x x 1 Input 2 x 0 x x 1 Input 3 x x 0 x 1 Input 4 x x x 0 1 Output 1 0 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Five-input AND Evaluation
Input 1 0 x x x x 1 Input 2 x 0 x x x 1 Input 3 x x 0 x x 1 Input 4 x x x 0 x 1 Input 5 x x x x 0 1 Output 1 0 0 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF
144
Command Reference: Logic Functions
Truth Table for Six-input AND Evaluation
Input 1 0 x x x x x 1 Input 2 x 0 x x x x 1 Input 3 x x 0 x x x 1 Input 4 x x x 0 x x 1 Input 5 x x x x 0 x 1 Input 6 x x x x x 0 1
Section 8-4
Output 1 0 0 0 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Seven-input AND Evaluation
Input 1 0 x x x x x x 1 Input 2 x 0 x x x x x 1 Input 3 x x 0 x x x x 1 Input 4 x x x 0 x x x 1 Input 5 x x x x 0 x x 1 Input 6 x x x x x 0 x 1 Input 7 x x x x x x 0 1 Output 1 0 0 0 0 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Eight-input AND Evaluation
Input 1 0 x x x x x x x 1 Input 2 x 0 x x x x x x 1 Input 3 x x 0 x x x x x 1 Input 4 x x x 0 x x x x 1 Input 5 x x x x 0 x x x 1 Input 6 x x x x x 0 x x 1 Input 7 x x x x x x 0 x 1 Input 8 x x x x x x x 0 1 Output 1 0 0 0 0 0 0 0 0 1
0: OFF, 1: ON, x: Either ON or OFF
145
Command Reference: Logic Functions
Section 8-4
8-4-3
Diagram
OR
Default
Maximum Number of Inputs
General Description
An OR of the input conditions will be output. Up to eight input conditions can be evaluated.
Optional Input Setting
The number of inputs can be increased on In/Out Setting Tab Page in the function block property dialog box.
Parameter Number of inputs Setting range 1 to 8 Default setting 2
Truth Table
Truth Table for One-input OR Evaluation
Input 1 0 1 Output 1 0 1
0: OFF, 1: ON Truth Table for Two-input OR Evaluation
Input 1 0 1 x Input 2 0 x 1 Output 1 0 1 1
0: OFF, 1: ON, x: Either ON or OFF
146
Command Reference: Logic Functions
Truth Table for Three-input OR Evaluation
Input 1 0 1 x x Input 2 0 x 1 x Input 3 0 x x 1 Output 1 0 1 1 1
Section 8-4
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Four-input OR Evaluation
Input 1 0 1 x x x Input 2 0 x 1 x x Input 3 0 x x 1 x Input 4 0 x x x 1 Output 1 0 1 1 1 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Five-input OR Evaluation
Input 1 0 1 x x x x Input 2 0 x 1 x x x Input 3 0 x x 1 x x Input 4 0 x x x 1 x Input 5 0 x x x x 1 Output 1 0 1 1 1 1 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Six-input OR Evaluation
Input 1 0 1 x x x x x Input 2 0 x 1 x x x x Input 3 0 x x 1 x x x Input 4 0 x x x 1 x x Input 5 0 x x x x 1 x Input 6 0 x x x x x 1 Output 1 0 1 1 1 1 1 1
0: OFF, 1: ON, x: Either ON or OFF
147
Command Reference: Logic Functions
Truth Table for Seven-input OR Evaluation
Input 1 0 1 x x x x x x Input 2 0 x 1 x x x x x Input 3 0 x x 1 x x x x Input 4 0 x x x 1 x x x Input 5 0 x x x x 1 x x Input 6 0 x x x x x 1 x
Section 8-4
Input 7 0 x x x x x x 1
Output 1 0 1 1 1 1 1 1 1
0: OFF, 1: ON, x: Either ON or OFF Truth Table for Eight-input OR Evaluation
Input 1 0 1 x x x x x x x Input 2 0 x 1 x x x x x x Input 3 0 x x 1 x x x x x Input 4 0 x x x 1 x x x x Input 5 0 x x x x 1 x x x Input 6 0 x x x x x 1 x x Input 7 0 x x x x x x 1 x Input 8 0 x x x x x x x 1 Output 1 0 1 1 1 1 1 1 1 1
0: OFF, 1: ON, x: Either ON or OFF
8-4-4
Diagram
Exclusive OR (EXOR)
General Description
An exclusive OR of the input conditions will be output.
148
Command Reference: Logic Functions Truth Table
Truth Table for Exclusive OR Evaluation
Input 1 0 0 1 1 Input 2 0 1 0 1 Output 1 0 1 1 0
Section 8-4
0: OFF, 1: ON
8-4-5
Diagram
Exclusive NOR (EXNOR)
General Description
An exclusive NOR of the input conditions will be output.
Truth Table
Truth Table for Exclusive NOR Evaluation
Input 1 0 0 1 1 Input 2 0 1 0 1 Output 1 1 0 0 1
0: OFF, 1: ON
8-4-6
Diagram
Reset Set Flip-Flop (RS-FF) Unit Ver. 1. 0 or Later
Input RESET
Output Enable
Input RESET
Output Enable Fault Present
Default
Maximum Number of I/O
149
Command Reference: Logic Functions General Description
Section 8-4
This function can be used with Controllers with unit version 1. 0 or later (including Controllers that support EtherNet/IP). When the input condition to the Reset Set Flip-Flop function block is turned ON, that ON status is maintained (latched) in the function block and the ON output is maintained at the Output Enable signal. The ON status is maintained in the function block, so the Output Enable signal stays ON even if the input condition goes from ON to OFF. The signal maintained in the function block is turned OFF when the function block's RESET condition is turned ON.
Fault Present Output Setting
A Fault Present output can also be used in programming. To enable this output, select the Fault Present checkbox on the Out Point Tab Page of the function block properties dialog box.
Error Handling and Error Resetting
Error condition Input and Reset are active simultaneously. Behavior for error detection Output Enable Fault Present OFF ON (safety state) Resetting the error condition Make one of the signals inactive.
Timing Table
Input
RESET Output Enable Fault Present
150
Command Reference: Logic Functions
Section 8-4
8-4-7
Diagram
Comparator Unit Ver. 1. 0 or Later
Input1
Output Enable
Input1 Input2 Input3 Input4 Input5 Input6 Input7 Input8
Output Enable
Default
Maximum Number of Inputs
General Description
This function can be used with unit version 1. 0 or later (including Controllers that support EtherNet/IP). The Comparator function block compares the specified input signals (up to 8 inputs) with the comparison data set in the Configurator, and turns ON the Output Enable signal when all of the input signals match the comparison data. The Output Enable signal will be turned OFF when the input signals no longer match the comparison data. From 1 to 8 inputs can be set for the input signals.
Set Parameters
Parameter Comparison Data Setting range Default setting 00000000 to 11111111 00000001 (Input 1 is ON. ) (Individual bits correspond to Input 1 to Input 8)
Optional Input Settings
The number of inputs can be increased on the In/Out Setting Tab Page in the function block property dialog box.
Parameter Number of inputs Setting range 1 to 8 Default setting 1
151
Command Reference: Logic Functions Truth Table
Section 8-4
Truth Table for Comparator Evaluation (CD = Comparison Data):
Input signals to Comparator Output signals from Comparator Input 7 × Input 8 × Output Enable 0
Input 1 CD for Input 1 ×
Input 2 ×
Input 3 ×
Input 4 ×
Input 5 ×
Input 6 ×
CD for Input 2 ×
×
×
×
×
×
×
0
×
CD for Input 3 ×
×
×
×
×
×
0
×
×
×
×
×
CD for Input 4 ×
×
×
×
×
0
CD for Input 5 ×
×
×
×
0
×
×
×
×
×
×
×
×
×
CD for Input 6 ×
×
×
0
CD for Input 7 ×
×
0
×
×
×
×
×
×
= CD for Input 1
= CD for Input 2
= CD for Input 3
= CD for Input 4
= CD for Input 5
= CD for Input 6
= CD for Input 7
CD for Input 8 = CD for Input 8
0
1
0: OFF; 1: ON Note "= CD for Input n" indicates that the Comparator input signals are the same as the comparison data. " CD for Input n" indicates that the Comparator input signals are not the same as the comparison data. "×" indicates that the status is not applicable (the input signals and comparison data may or may not be the same).
152
Command Reference: Logic Functions Timing Chart
Section 8-4
Output Enable
1
2
The horizontal broken lines in the above diagram represent the comparison data for each input. Output Enable turns ON when all of the input signals match the comparison data. Output Enable turns OFF when any of the input signals does not match the comparison data.
153
Command Reference: Function Blocks
Section 8-5
8-5
8-5-1
Command Reference: Function Blocks
Reset
Diagram
Reset Monitored Input
Output Enable
Default
Maximum Number of Inputs
General Description
The Output Enable signal will turn ON if the Reset signal is correctly input while the input condition to the Reset function block is ON. This function block can be used to prevent the machine from automatically reset, e. g. , when the power to the NE1A-series Controller is turned ON, when the operating mode is changed (from IDLE Mode to RUN Mode), or when a signal from a safety input device turns ON. Conditions for Output Enable Turning ON · The Monitored Input and all enabled optional inputs must be ON. Conditions for Static Release Turning ON The Monitored Input and all enabled optional inputs must be ON. Conditions for Reset Required Indication Turning ON If the following condition is met, the Reset Required Indication will become a 1-Hz pulse output. · The Monitored Input and all enabled optional inputs must be ON. If the Reset Signal is set to Low-High-Low, the Reset Required Indication will turn ON when the next condition is met. [. . . ] With a single-cast connection, a Safety Master and Safety Slave communications 1:1. This connection can be set for either an input or an output, and separate connections are needed for each. In this manual, items used for general control purposes are called "standard" to differentiate them from devices, functions, data, and other items for which which safety measures have been applied. A CPU Unit used for standard control, such as CPU Units in OMRON's CS or CJ Series. [. . . ]