Manual abstract: user guide OMRON E5EK
Detailed instructions for use are in the User's Guide.
[. . . ] H085-E1-03
Preface
Thank you for your purchase of your E5EK, intelligent digital controller. The E5EK allows the user to carry out the following: · Select from many types of temperature and analog input (multiple input) · Support position-proportional control (position-proportional type controllers only). · Select output functions such as control output or alarm (output assignment) · Use the HBA (heater burnout alarm) function (standard type controllers only). · Use four setpoints (multi-SP function) · Use remote SP input. [. . . ] After AT execution, the "PID" and the "LBA detection time" (LBA: Loop Break Alarm) parameters are set automatically. · During heating and cooling control or position-proportional control, only 100%AT can be executed. · When this parameter is selected, the setting becomes [ ], and to execute 100%AT, select [ ]. During · To execute 40%AT, select [ execution of auto-tuning, the AT LED flashes. However, note that during heating and cooling control or position-proportional control, [ ] is not displayed. · When AT execution ends, the parameter setting automatically returns to [ ]. F Related article 3. 7 Adjusting Control Operation (page 3-16) F Related parameters "Run/Stop" (level 0 mode) "Proportional band" "Integral time" "Derivative time" (level 1 mode) "LBA detection time" (level 2 mode)
Example of use
See
Set point 0 Set point 1
Set point 2 Set point 3
Conditions of Use The controller must be in the local SP mode with the multi-SP function enabled.
Function
· Switches set points 0 to 3 by event input for use as the set point (local SP). · Of set points 0 to 3, the number of valid set points is designated by the "multi-SP function" parameter. · The following table shows the relationship between event input and the selected parameter.
Multi-SP Function Event Input Set Point 0 Set Point 1 Set Point 2 Set Point 3 1 1 OFF ON 1 OFF ON OFF ON 2 2 OFF OFF ON ON
· When the set point has been changed, the setting of whichever is selected in event input, "set point 0" to "set point 3", is linked and changed. · The decimal point position is dependent on the selected sensor during temperature input and on the results of scaling during analog input. 5--11
CHAPTER 5 PARAMETERS
Level 1 Mode
Setting Range Set point lower limit to Set point upper limit
Comment
Unit EU
Default 0
See
F Related article 4. 3 How to Use Event Input (page 4-8) F Related parameters "Multi-SP function" "Remote SP enable" (option mode) "Set point" (level 0 mode) "SP mode" (level 2 mode) "Input type" "Scaling upper limit" "Scaling lower limit" "Decimal point" (setup mode) F Option unit E53-AKB
Model
Alarm value 1 Alarm value 2 Alarm value 3
Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the "alarm value 3" parameter cannot be used.
Function
· This parameter is used for monitoring or changing the alarm values of alarm outputs 1 to 3. · During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling.
Setting Range -1999 to 9999 Unit EU Default 0
Comment
See
F Related article 3. 4 Setting Alarm Type (page 3-9) F Related parameters "Input type" "Scaling upper limit" "Scaling lower limit" Decimal point" "Control output 1 assignment" "Control output 2 assignment" "Auxiliary output 1 assignment" "Auxiliary output 2 assignment" "Alarm 1 type" "Alarm 2 type" "Alarm 3 type" "Alarm 1 open in alarm" "Alarm 2 open in alarm" "Alarm 3 open in alarm" (setup mode) "Alarm 1 hysteresis" "Alarm 2 hysteresis" "Alarm 3 hysteresis" (level 2 mode) "Standby sequence reset method" (expansion mode)
5--12
Level 1 Mode
Proportional band Integral time Derivative time
Conditions of Use Control must be advanced PID control, and ST must be set to OFF.
Function
· Sets the PID parameters. However, note that the PID parameter settings are changed to optimum values when auto-tuning is executed, and self-tuning is selected.
Comment
Parameter Proportional band Integral time Derivative time
Setting Range 0. 1 to 999. 9 0 to 3999 (see note1) 0 to 3999
Unit %FS Second Second
Default 10. 0 233 40
note1 : During position-proportional control, the setting range become 1 to 3999s. F Related parameter "AT Execute/Cancel" (level 1 mode)
See
Cooling coefficient
Conditions of Use The control must be either heating and cooling control, or advanced PID control.
Function
· In heating and cooling control, P at the cooling side is calculated by the following formula: Cooling side P = cooling coefficient ¢ P
Setting Range 0. 01 to 99. 99
Comment
Unit None
Default 1. 00
F Related article 4. 1 Selecting the Control Method (page 4-2)
See
F Related parameter "Proportional band" (level 1 mode) E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
5--13
CHAPTER 5 PARAMETERS
Level 1 Mode
Dead band
Conditions of Use The control system must be heating and cooling control.
· Sets the output dead band width in a heating and cooling control system. A negative setting sets an overlap band.
Function
Setting Range -19. 99 to 99. 99
Comment
Unit %FS
Default 0. 00
F Related article 4. 1 Selecting the Control Method (page 4-2)
See
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
Position-proportional dead band
Conditions of Use Control must be position-proportional control
· Sets the output hold width during position-proportional control (ON/OFF switching point for open and close output).
Function
Open/close hysteresis Dead band ON OFF
-100% Setting Range 0. 1 to 10. 0
Comment
0 Unit % 2. 0
MV--Valve opening Default
100%
See
F Related article 4. 1 Selecting the Control Method/Position-proportional Control (page 4-3). F Related parameter "Open/close hysteresis" (level 2 mode) E5EK-PRR2 AC100-240 E5EK-PRR2 AC/DC24
Model
5--14
Level 1 Mode
Manual reset value
Conditions of Use The control must be either standard control or advanced PID control, ST must be set to OFF, and the "integral time" parameter must be set to "0".
· Sets the required manipulated variable to remove offset during stabilization of P or PD control.
Function
Setting Range 0. 0 to 100. 0
Comment
Unit %
Default 50. 0
E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
Hysteresis (heat) Hysteresis (cool)
Conditions of Use The control system must be ON/OFF control.
· Sets the hysteresis for ensuring stable operation at ON/OFF switching.
Function
· In standard control, use the "hysteresis (heat)" parameter. · In heating and cooling control, the hysteresis can be set independently for heating and cooling. Use the "hysteresis (heat)" parameter to set the heating side hysteresis, and use the "hysteresis (cool)" parameter to set the cooling side hysteresis.
Comment
Parameter Hysteresis (heat) Hysteresis (cool)
Setting Range 0. 01 to 99. 99 0. 01 to 99. 99
Unit %FS %FS
Default 0. 10 0. 10
See
F Related article 4. 1 Selecting the Control Method/ON/OFF control (page 4-4) F Related parameters "Control output 1 assignment" "Control output 2 assignment" (setup mode) "PID / ON/OFF" (expansion mode) E5EK-AA2 AC100-24 E5EK-AA2 AC/DC24
Model
5--15
CHAPTER 5 PARAMETERS
Level 1 Mode
Control period (heat) Control period (cool)
Conditions of Use Relay or voltage output must be set as the outputs, and the control must be set to advanced PID control, standard control or heating and cooling control.
· Sets the pulse output period. Set the control period taking the control characteristics and life expectancy of the controller into consideration.
Function
· In standard control, use the "control period (heat)" parameter. · In heating and cooling control, the control period can be set independently for heating and cooling. Use the "control period (heat)" parameter to set the heating side control period, and use the "control period (cool)" parameter to set the cooling side control period.
Parameter Control period (heat) Control period (cool) Setting Range 1 to 99 1 to 99 Unit Second Second Default 20 20
Comment
F Related article 3. 3 Setting Output Specifications (page 3-6)
See
F Related parameters "Control output 1 assignment" "Control output 2 assignment" (setup mode) E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
5--16
Level 1 Mode
Heater current monitor
Conditions of Use The HBA output function must be assigned.
· Measures the current value of the heater from CT input.
Function
Monitor Range 0. 0 to 55. 0
Monitor
Unit A
·[
] is displayed when 55. 0 A is exceeded.
F Related article 4. 5 How to Use the Heater Burnout Alarm (page 4-13)
See
F Related parameters "Heater burnout" (level 1 mode) "HBA latch" (option mode) E5EK-AA2 AC100-240 E5EK-AA2 AC/DC24
Model
Heater burnout
Conditions of Use The HBA output function must be assigned.
· Outputs the heater burnout alarm when the heater current value falls below this parameter setting.
Function
· When the set value is "0. 0", the heater burnout alarm is "OFF". [. . . ] Added "Model" and "Power specifications" to Dead band. Added "Model" and "Power specifications" to Position-proportional dead band. Added "Model" and "Power specifications" to Manual reset value. Added "Model" and "Power specifications" to Hysteresis. [. . . ]