Detailed instructions for use are in the User's Guide.
[. . . ] terminal cover E5CSV-R1T-500 E5CSV-Q1T-500 E5CSV-R1TD-500 E5CSV-Q1TD-500
Accessories (Order Separately)
Protective Front Cover
Type Hard Protective Cover Model Y92A-48B
4
Temperature Controllers E5CSV Temperature Controllers E5CSV 1
Specifications
Ratings
Supply voltage Operating voltage range Power consumption Sensor input Control output Relay output 100 to 240 VAC, 50/60 Hz 85% to 110% of rated supply voltage 5 VA SPST-NO, 250 VAC, 3A (resistive load) ON/OFF or 2-PID (with auto-tuning) SPST-NO, 250 VAC, 1A (resistive load) Digital setting using front panel keys (functionality set-up with DIP switch) 3. 5 digit, 7-segment digital display (character height: 13. 5 mm) and deviation indicators · · · · · · · Setting change prohibit (key protection) Input shift Temperature unit change (° C/° F) Direct/reverse operation Control period switching 8-mode alarm output Sensor error detection 3 VA/2 W Multi-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100 24 VAC/VDC, 50/60 Hz
Voltage output (for driving the SSR) 12 VDC, 21 mA (with short-circuit protection circuit)
Control method Alarm output Setting method Indication method Other functions
Ambient temperature Ambient humidity Storage temperature
-10 to 55° C (with no condensation or icing) 25% to 85% -25 to 65° C (with no condensation or icing)
Characteristics
Setting accuracy Indication accuracy (ambient temperature of 23° C) Influence of temperature Influence of voltage Hysteresis (for ON/OFF control) Proportional band (P) Integral time (I) Derivative time (D) Alarm output range Thermocouple (See note 1. ): (±0. 5% of indication value or ±1° C, whichever is greater) ±1 digit max. Platinum resistance thermometer (See note 2. ): (±0. 5% of indication value or ±1° C, whichever is greater) ±1 digit max. R thermocouple inputs: (±1% of PV or ±10° C, whichever is greater) ±1 digit max. Other thermocouple inputs: (±1% of PV or ±4° C, whichever is greater) ±1 digit max. [. . . ] When using a grounding thermocouple, do not connect output terminals 1 or 2 to ground. Models using 24 VDC have no polarity.
6
Temperature Controllers E5CSV Temperature Controllers E5CSV 3
Operation
E5CSV
Deviation indicators
The indicator lights when the PV is greater than the SP and the indicator lights when the PV is less than the SP. The indicator (green) lights when the deviation is less than 1% FS (0. 25% FS for multi-input models). These indicators flash during ST (self-tuning)/AT (auto-tuning).
PV, SP, Alarm Value, Input Shift Display
The display switches each time the Key is pressed.
Output indicator
Lights when the control output is ON.
Mode indicators
The SP indicator lights when the setting temperature is being displayed. The ALM indicator lights when the alarm value 1 is being displayed.
Alarm indicators
ALM1 (Alarm 1): Lights when the alarm 1 output is ON. ALM2 (Alarm 2): For future use.
Mode Key
When the power is turned ON, normally the display will use the display items in the following order each time the Mode Key is pressed.
Power ON
Up Key
Pressing the Up Key increases the SP/alarm value display. When the internal protect switch is ON, press the Up Key while holding down the Lock Release Key.
PV Press the SP Press the Alarm value 1 Press the
Input shift value
Key.
Key.
Down Key Lock Release Key
When the protect switch is ON, the set value can be changed by pressing the Up and Down Keys while holding down the Lock Release Key. When the internal protect switch is ON, press the Down Key while holding down the Lock Release Key.
Key. Key.
Press the
Settings before Turning ON the Power
E5CSV
Remove the E5CSV from the case to make the settings. Insert the tool into the two tool insertion holes (one on the top and one on the bottom) and release the hooks.
Tool insertion hole Flat-blade screwdriver (Unit: mm)
3. When inserting the E5CSV, check to make sure that the sealing rubber is in place and push the E5CSV toward the rear case until it snaps into position. While pushing the E5CSV into place, push down on the hooks on the top and bottom surfaces of the rear case so that the hooks are securely locked in place. The input indication range is the range that can be displayed for the control range (-99 to 1999). If the input is within the control range but exceeds the display range (-99 to 1999), values below -99 will be displayed as "[[[" and values above 1, 999 will be displayed as "]]]. " 2. If unit is changed to 1 degree when the SP and alarm value for the temperature range are displayed in 0. 1-units from 0. 0 to 199. 9 or 0. 0 to 99. 9, the values will be multiplied by 10 (e. g. , 0. 5 becomes 5). If the unit is changed in the reverse direction, the values will be divided by 10. After changing the range, set the SP and alarm value again.
AT cancelled
Press for at least 2 s. AT execution in progress
Press for AT execution in progress at least 2 s.
UD
Note: One of the deviation indicators () will flash.
· Using Platinum Resistance Thermometers, Control Mode Switch 5: ON
Input
1, 000 900 800 700 600 500 400 300 200 100 0 -100 850
Pt100
JPt100
Electrical Life Expectancy Curve for Relays (Reference Values)
Life (× 104 operations) 500 300 100 50 30
SP range
400 199. 9 0. 0 99 -99 200 0 0
500 199. 9 0. 0 200 0
400 99 -99
-99
-99
0
Setting number
0
1
2
3
4
5
6
7
8
9
10 5 3 E5CSV 250 VAC, 30 VDC (resistive load) cos = 1 0 1 2 3 4 5 6
· The control range is -20° C to +20° C of the input temperature range.
Note: 1. The input indication range is the range that can be displayed for the control range (-99 to 1999). If the input is within the control range but exceeds the display range (-99 to 1999), values below -99 will be displayed as "[[[" and values above 1, 999 will be displayed as "]]]. " 2. If unit is changed to 1 degree when the SP and alarm value for the temperature range are displayed in 0. 1-units from 0. 0 to 199. 9 or 0. 0 to 99. 9, the values will be multiplied by 10 (e. g. , 0. 5 becomes 5). If the unit is changed in the reverse direction, the values will be divided by 10. [. . . ] Performing Control via Relay Output, External Relay, or Conductor Switch 2: OFF (control period: 20 s)
ON
2. Performing Heating Control for Heaters Switch 3: OFF
ON
1
2
3
4
5
6
1
2
3
4
5
6 Output level
Control output ON OFF 20 s
100% 0% SP
Quick Control Response Using an SSR Switch 2: ON (control period: 2 s)
ON
Performing Cooling Control for Freezers Switch 3: ON
ON
1
2
3
4
5
6
1
2
3
4
5
6 Output level
Control output ON OFF 2s 100% 0% SP
10
Temperature Controllers E5CSV Temperature Controllers E5CSV 7
(2) Using the E5CSV in Devices for Fahrenheit-scale Users
(Displaying in ° F) Turn ON switch 6 to display temperatures in ° F.
ON
1
2
3
4
5
6
Temperature Range for ° F
The temperature is set to ° F using the same temperature range switch as ° C. Multi-input (Thermocouple/ Platinum Resistance Thermometer) Control mode switch 5: OFF Setting 0 1 2 3 4 5 6 7 8 9 U N R L T J K °F -99 to 1999 0. 0 to 199. 9 -99 to 1500 0. 0 to 199. 9 -99 to 1500 -99 to 700 0. 0 to 199. 9 -99 to 700 -99 to 1999 0 to 1999 Multi-input (Thermocouple/ Platinum Resistance Thermometer) Control mode switch 5: ON Setting 0 1 2 3 4 5 6 7 8 9 JPt100 Pt100 °F -99 to 1500 0. 0 to 199. 9 -99 to 99 0 to 200 0 to 400 -99 to 900 0. 0 to 199. 9 -99 to 99 0 to 200 0 to 400
Note: The control range for multi-input (thermocouple/platinum resistance thermometer) models is -40 to +40° F of each temperature range. The previous name J-DIN has been changed to L in accordance with revisions to DIN standards.
(3) Setting Input Shift
Turn ON switch 4, and after turning ON the power, press the Mode Key until h0 (indicates input shift of 0) is displayed. [. . . ]