[. . . ] XL 1000 Series
FOR SMOKE CONTROL
HONEYWELL EXCEL 5000 OPEN SYSTEM
INSTALLATION AND COMMISSIONING INSTRUCTIONS CONTENTS
Operational Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Before Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . [. . . ] 3).
EN1B-0409GE51 R0908A
10
XL1000
Mounting
Allow 30 mm clearance for opening swivel cover.
step 1
190
LON CF
LON
1
2
3
100 mm
Allow 30 mm clearance for accessing interfaces. 36. 5 278 4. 4 +/- 0. 3
step 3 step 4
0. 6
60. 6
step 2
fastening plate
141. 5 +/- 0. 3
Fig. Mounting the XL1000 onto two DIN rails
12 220 +/- 0. 3 5 +/- 0. 3
Wall/Panel Mounting/Dismounting
The XL1000 can be mounted on walls or in panels in any desired orientation. However, mounting the XL1000 upside down on ceilings should be avoided, insofar as the swivel cover would then swing open.
Fig. Dimensions (in mm)
DIN Rail Mounting/Dismounting
17 mm
4. 4 +/- 0. 3 36. 5 141. 5 +/- 0. 3 190
slots for DIN rails (center-to-center distance = 100 +3 mm)
12 29
fastening plate
220 +/- 0. 3 278
29
Fig. Housing base (view from below) The XL1000 can be mounted onto DIN rails as follows (refer also to Fig. Slide the fastening plate and corresponding screw in the oval hole up against and behind the bottom edge of the lower DIN rail and screw it firmly into place. If necessary, the swivel cover can be locked by inserting a small string lock, lead seal, or screw into either one of the two openings provided. The unit is dismounted by loosening the fastening plate and lifting the unit out of place.
Fig. Drilling template (view from above)
Swivel Cover Lock
The swivel cover can be locked by inserting a small string lock, lead seal, or screw into either one of the two openings provided (see Fig. 11).
11
EN1B-0409GE51 R0908A
5 +/- 0. 3
Power Supply
XL1000
Power Supply
Power is supplied via terminals 1 and 2 of the lower removable terminal plug. The removable terminal plug permits individual XL1000 controllers to be disconnected from the power supply without disturbing the operation of other devices powered by the same source.
24 VAC CONTROLLER POWER SWITCH 120 VAC, 60 HZ LINE INPUT
NOTE: Do not reverse the polarity of the power connection cables, and avoid ground loops (i. e. avoid connecting one field device to several controllers) as this may result in short-circuiting.
MAIN LINE VOLTAGE 120 VAC, 60 HZ TERMINAL "G" MUST BE CONNECTED TO A GOOD EARTH GROUND.
* H N G
CONTROLLER POWER ON OFF CONTROLLER SUPPLY 24VAC 48VA
2 AMP F1
FUSE F1 (2 AMPS) PART NUMBERS ARE AS FOLLOWS: HONEYWELL PART NO. 14000485-007 (AVAILABLE FROM HONEYWELL BRANCH LOCATIONS, ONLY) BUSSMAN PART NO. with 14507287 power modules 14507287-001 through -003, only. ) CONNECTOR TO XL1000 CONTROLLER J5 BRN GRN BLK
MUST BE WIRED TO EARTH GROUND
"G" MUST BE
WIRED TO EARTH GROUND
UNSWITCHED UNFILTERED 120 VAC
CONNECTORS ARE KEYED TO PREVENT MISALIGNMENT. CONVENIENCE OUTLET (UNFILTERED, UNSWITCHED) -001 = 120 VAC, 10 AMP * 14507287-001 POWER TERMINALS LABELED H-N-G.
Fig. Typical 14507287-001 Power Module wiring
24 VAC CONTROLLER POWER SWITCH
120 VAC, 60 HZ LINE INPUT 2 AMP F1 ON OFF 2 AMP F3 5 AMP F2
120 VAC, 60 HZ LINE INPUT 24VAC ACCESSORY POWER -002 AND -003 MODELS (4 AMP MAX. )
MAIN LINE VOLTAGE 120 VAC, 60 HZ TERMINAL "G" MUST BE CONNECTED TO A GOOD EARTH GROUND.
* H N G
CONTROLLER POWER ON OFF
~
CONTROLLER SUPPLY MUST BE WIRED TO EARTH GROUND 24VAC 48VA
~
G 14507063-002 POWER CABLE (incl. with 14507287 power modules 14507287-001 through -003, only. ) CONNECTOR TO XL1000 CONTROLLER J5 BRN GRN BLK 24 VAC ACCESSORY POWER -002 MODEL, ONLY. FOR 14507287-003 (24VDC) BRN GRY BRN GRY FOR 14507287-002 (24VAC) RED BRN GRY GRY UNSWITCHED UNFILTERED 120 VAC
"G" MUST BE WIRED TO EARTH GROUND
CONNECTORS ARE KEYED TO PREVENT MISALIGNMENT. CONVENIENCE OUTLET (UNFILTERED, UNSWITCHED) -002 AND -003 = 10 AMP
* 14507287-001 POWER TERMINALS LABELED H-N-G. POWER MODULE 14507287-001 THROUGH -003 14507287-002 AND -003 14507287-002 AND -003
FUSE NO.
FUSE RATING
HONEYWELL PART NO.
BUSSMAN PART NO.
LITTLEFUSE PART NO.
F1 F2 F3
2 AMPS 5 AMPS 2 AMPS
14000485-007 14507374-001 14000485-007
AGC-2 GMA 5AMP AGC-2
312002 235005 312002
Fig. Typical 14507287-002, -003 Power Module wiring
EN1B-0409GE51 R0908A
12
XL1000
Power Supply
CONTROLLER TRANSFORMER
CONTROLLER SUPPLY 24 VAC 48 VA G 70 ~ 71 72
GRN
BRN BLK
3 4
1
H N G
BLK WHT GRN
24 V 50 VA 14507351-001 429P156A E1A 1052 XXXX COM 120 V
MAIN LINE (120 VAC, 60 Hz) TERMINAL "G" MUST BE CONNECTED TO A GOOD EARTH GROUND.
1
2
1
1
MECHANICALLY SECURED TO SUBPANEL WITH MOUNTING SCREW
Fig. [. . . ] PROTECTED SWITCHING UP TO 40 VDC / 24 VAC.
3
15
2
5 TO 24 VDC
1
~ 120V
PT1000 NTC20kW
Fig. XFL823AU Binary Input Module, connection to field devices
27
EN1B-0409GE51 R0908A
Description of the I/O Modules
XL1000
Relay Output Modules
Types of Relay Output Modules
Table 20. XL800 Relay Output Modules type XFL824 XFLR824 XS824-25 description housing
Terminals
72 COM B 73 74
24 V~ 24 V~0
71 COM A
COM A COM B 24 V~ 24 V~0
75 76 77 78
LONWORKS Relay Output Module dark-gray LONWORKS Relay Output Module dark-gray with manual overrides terminal socket; can be fitted with long (red) cross connector (incl. in scope of the delivery) light-gray
NO NC COM CON
Relay block 1
Relay block 2
11 12 13 14
NO 21 NC 22 COM 23 CON 24
NO NC COM CON
31 32 33 34
NO NC COM CON
41 42 43 44
NO NC COM CON
51 52 53 54
NO NC COM CON
61 62 63 64 25
Cross connector (can be removed, as desired)
Features
· 6 relays (changeover contacts), arranged in two blocks · XFLR824AU: 6 manual overrides · Low and line voltage allowed, see WARNING.
Fig. [. . . ]