If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual FIELD CONTROLS 46360900. We hope that this FIELD CONTROLS 46360900 user guide will be useful to you.
Manual abstract: user guide FIELD CONTROLS 46360900
Detailed instructions for use are in the User's Guide.
[. . . ] determining your homes needs.
Model Minimum Duct Width Volts Amps Hz Watts Max Air Temp °F Lamp Intensity at 1 meter
II.
See chart below for
Recommended Max Sq. Feet
UV-12 UV-18
9 14
120 120
0. 5 0. 5
60 60
30 30
190° 190°
37 µW/cm2 73 µW/cm2
1500 2000
WARNING: Before installing or servicing a humidifier, air filter, heat system, or this unit, etc. , always turn all power OFF and have unit unplugged. WARNING: To prevent water damage or electric shock, do not mount unit under a humidifier. For use on gas fired, oil fired, electric and split system heat pump forced air systems*. [. . . ] Bend both tabs at the second bend point up or down to pinch the duct material and grip the duct material. Using a screwdriver or pointed object, locate mounting holes by poking holes through the duct tape. (See Figure 11)
Figure 3
Figure 4
Figure 5
Figure 6
Figure 7
Figure 8
Figure 9
Figure 10
Figure 11
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Apply supplied "Duct Seal Kit" according to instructions included in kit (See Figure 12)
Figure 12
5. (Refer to UV-Aire "Bulb Mounting Bracket Selection" in section IV for aid in this decision) a. Remove the two hex nuts and flat bracket from included bagged hardware. Install the flat bracket and secure to the unit base with the hex nuts provided. Angled Bracket Installation NOTE: For angled bracket mounting, refer to specifications outlined by Diagrams A & B for mounting distances in the "Angled Lamp Mounting Bracket Specifications" in section IV. Remove the two hex nuts and angled bracket from included bagged hardware. Install the angled bracket and secure to the unit base with the hex nuts provided. (See Figure 14) NOTE: Be sure to note location of lamp hole in bracket relative to unit base.
Figure 14
6. Mount the unit base to the duct using the four mounting screws provided. The oils from your hands will reduce lamp output.
Figure 15
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. The porcelain at the lamp base may crack when over tightened.
Figure 16
Figure 17
10. Plug the power cord into a standard electrical outlet.
Figure 19
NOTE: Seal the joints and seams of the plenum near the mounting location to reduce any direct viewing of light. (The view port is covered with a plastic lens that blocks the UVC rays. ) 15. If lamp still does not glow, contact technical support at 1-252522-3031 for further assistance.
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. [. . . ] If the lamp still does not light up after replacing the lamp, replace ballast.
VIII.
REPLACEMENT PARTS LIST MODEL UV-12 UV-18 LAMP (Field Controls Part Number) 46365401 46365402 BALLAST (Field Controls Part Number) 46365508 46365509
For replacement parts, contact your local heating service company. Any questions, please contact Field Controls at: !Phone: 252-522-3031 "Fax: 252-522-0214 #Email: sales@fieldcontrols. com
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness. Page 7
IX.
FLEX DUCT INSTALLATION For installations on duct systems with a metallic main duct and flex duct branches, follow the instructions in figure 21 below.