User manual BENSHAW RTD MODULE
DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!
If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual BENSHAW RTD MODULE. We hope that this BENSHAW RTD MODULE user guide will be useful to you.
Manual abstract: user guide BENSHAW RTD MODULE
Detailed instructions for use are in the User's Guide.
[. . . ] INTRODUCTION
The connection wire from the Remote RTD Module to the RTD will typically have all three conductors the same size and length. From the above, the following equations can be seen; VRH = VR lead + VRTD + VH lead = 20mA ´ Rlead +10mA ´ RRTD +10mA ´ Rlead VCR = VC lead + VR lead = 10mA ´ Rlead + 20mA ´ Rlead Subtracting these two equations and subsituting Rlead for the different lead resistance provides the following; VRH - VCR = (30mA ´ Rlead + 10mA ´ RRTD) - (30mA ´ Rlead) VRH - VCR = 10mA ´ RRTD This calculation gives the voltage across the RTD independant of the connection wire resistance. By performing this calculation, the Remote RTD Module compensates for the conductor resistance and gets the true value for the RTD resistance. The Remote RTD Module then converts the measured voltage across the RTD to the temperature that the RTD is measuring. [. . . ] The connections are as follows; · A () - RS485 negative communications connection. The RS-485 communications cable should conform to the following specification; · Conductors - 2 twisted pair (one pair signal plus one for signal common). The RS-485 shield should be terminated at only one point in the network, preferably at the master device. A 120W resistor may optionally be installed between the A(-) and B(+) terminals if the Remote RTD Module is the end device on the RS-485 network. The terminating resistor may be necessary if the RS-485 cable is extremely long. Do not install a terminating resistor if the Remote RTD Module is not the end device on the network. There should never be more than two terminating resistors on the network.
RS-485 Cable Specification
RS-485 Topology
RS-485 Shielding
RS-485 Termination
8
3. INSTALLATION OF THE REMOTE RTD MODULE
3. 4
RTD Connections
RTD Wire Connections
Each Remote RTD Module has connections for up to 8 RTDs. The terminals for the RTD wires are as follows; · R - RTD return wire. For example, RTD number 5 connects to the terminals numbered 5R, 5C, and 5H. Benshaw recommends using 3-wire twisted (triad) shielded cable to connect the RTDs to the RTD module. It is important to keep the three wires of the same length and type for accurate lead resistance compensation. The RTD cable shield should be terminated at either of the shield terminals. For a simpler installation, a cable containing multiple triads with an overall shield can be used to connect a group of RTDs to the module with a single cable.
RTD Cable Specification
RTD Cable Shielding
3. 5
General
Wiring Diagram
The following is the wiring diagram detailing the connections of the RTD module. Only the wiring for RTD #5 is shown as the typical connection, but all the other RTDs connect similarly.
Status
Tx
Rx
BENSHAW
ADVANCED CONTROLS & DRIVES
Remote RTD Module
3C 7C 3R 7R 4H 8H 4C 8C 4R 8R Com 24 VDC + A (-) B (+)
RS-485
1H 5H
1C 5C
1R 5R
2H 6H
2C 6C
2R 6R
Shld Shld
3H 7H
24 VDC Power Supply
VV+
RS-485 Master Device
Shld B(+) A(-) Com
H
C R
RTD #5 (Typical)
9
4. COMMUNICATING WITH THE REMOTE RTD MODULE
4. 1
General
Modbus Communications
The Remote RTD Module uses an industry standard RS-485 port, communicating as a Modbus RTU slave. The Remote RTD Module has the following communications features; · RS-485 port. · Modbus RTU slave, addresses 16 to 23.
4. 2
General
Modbus Input Registers
The Benshaw Remote RTD Module has a number of Modbus input registers. These registers are used to read the temperatures measured by the eight RTDs. The following table lists the Modbus input registers; Register 30001 30002 30003 30004 30005 30006 30007 30008 30009 Description RTD 1 RTD 2 RTD 3 RTD 4 RTD 5 RTD 6 RTD 7 RTD 8 Shorted RTD Values 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius 0 to 200 - Temperature in degrees Celsius A bit is set if an RTD has a shorted lead. [. . . ] · Byte 2: Function code with the most significant bit set to 1 to indicate an exception. · Byte 3: Exception code 02h indicating an illegal data address exception. For example, if an attempt is made to read a holding register that does not have a valid address, the Remote RTD Module will respond with the following; Address 10h Function Code 83h Exception Code 02h CRC code 90 F4h
Illegal Data Value
If the Remote RTD Module receives a preset single register command that contains an illegal value, it will respond with and illegal data value exception response. The response will be in the form; · Byte 1: RTD module address. [. . . ]
DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RTD MODULE
Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual BENSHAW RTD MODULE will begin.