User manual BENSHAW RSM11

DON'T FORGET : ALWAYS READ THE USER GUIDE BEFORE BUYING !!!

If this document matches the user guide, instructions manual or user manual, feature sets, schematics you are looking for, download it now. Diplodocs provides you a fast and easy access to the user manual BENSHAW RSM11. We hope that this BENSHAW RSM11 user guide will be useful to you.


BENSHAW RSM11 : Download the complete user guide (1119 Ko)

Manual abstract: user guide BENSHAW RSM11

Detailed instructions for use are in the User's Guide.

[. . . ] BENSHAW REDISTART MICRO II INSTRUCTION MANUAL RSM10/10B/11/11B SERIES Solid State Motor Control Technology Publication #: 890015-03-08 The Leader In TABLE OF CONTENTS Table of Contents 1. Computer Card JC11 Header Assignments RediStart Micro II Power Card Jumpers . 46 47 48 48 49 49 49 49 50 50 50 51 51 52 52 52 52 53 5. 2 PROGRAMMING: Quick Start . 55 55 55 56 56 ii TABLE OF CONTENTS 5. 6 PROGRAMMING: Starter Setup - Forward2 Profile . [. . . ] The default value for the ramp time is 15 seconds. 61 5. 8 PROGRAMMING: Starter Setup - Reverse2 Profile Coast Time Description The Coast Time parameter sets the time the starter will "coast" with no power applied to the motor if a change of direction is made while the starter is running. Caution must be taken when setting a short coast time and a high initial current. The starter will begin to apply power in the opposite direction once the coast time has expired and the high initial current setting will cause a high torque on the motor shaft. The coast time is adjustable from 0 to 90 seconds in 1 second increments. The default value for the coast time is 1 second. Values Default Kick Curr. (kick current) Description The kick current parameter is set as a percentage of the motor FLA parameter setting. The kick current sets a current level that overrides the current ramp profile, for the set kick time, when a start is commanded. If a kick time is programmed, the starter will provide the current level specified by the kick current setting for this set time. This current can be used to overcome the break over torque of some loads, while still allowing the starter to smoothly accelerate the load to full speed. The default value for the kick current is 300%. Values Default Kick Time Description The kick time parameter sets the amount of time that the kick current level is provided to the motor when a start is commanded. If the kick time is set to any time other than Off, the starter will provide the kick current level for the set time. The kick time should be increased or decreased to reach the time required to begin rotating the load. Values The kick time is adjustable from 0. 1 to 10. 0 seconds in 0. 1 second intervals. If a kick current is not required, the kick time should be set to Off. The default value for the kick time is Off. Default 62 5. 9 PROGRAMMING: Starter Setup - Jog Cntrl Setup Jog Curr. (jog current) Description The jog current parameter is set as a percentage of the motor FLA parameter setting. The jog current parameter is used to set the maximum current that will reach the motor while the motor is being operated in the jog at set speed mode. It should be set to the lowest possible current level that will still operate the motor. When a motor is operating in the jog at set speed mode, its cooling capability is greatly reduced. Therefore, the running time of the motor is dependant on the motor current. If the jog at set speed will be used on a regular basis, the motor temperature should be monitored using a thermostat. The thermostat can be connected between the power and input terminal 1 of the JC13 terminal block on the RediStart Micro II computer card so that the starter will trip when a fault occurs. [. . . ] Each line lists the parameter, page reference, blank, and default setting. The blank spot is for entering the programmed value so that a record of the entered parameters is kept. NOTE: Not all starters have all of the listed parameters. Recording Parameters Quick Start Parameter Quick Start Motor FLA Serv. Ramp Time Overload Phase Orde Page 49 49 49 49 50 50 50 51 51 Range 1-1200 1. 00-1. 99 Curr, TT, Tach Coas, VDCL, TT, Brak 50-400 100-600 0-120 see text INS, ABC, CBA 1 1 1 1 % % sec. [. . . ]

DISCLAIMER TO DOWNLOAD THE USER GUIDE BENSHAW RSM11




Click on "Download the user Manual" at the end of this Contract if you accept its terms, the downloading of the manual BENSHAW RSM11 will begin.

 

Copyright © 2015 - manualRetreiver - All Rights Reserved.
Designated trademarks and brands are the property of their respective owners.